27/52
L3016
1SDH000559R0002
ABB SACE
SACE PR021/K
5.9.2. Signals
The signals (K51/1...K51/8) for the SACE PR222DS protection release may be divided into 2 modes: Normal and Latch.
A description of the signals in these modes is given below.
5.9.2.1.
Normal mode (see par. 4.5.1)
Dip-switch no. 11 to be set to its OFF position.
Note 1:
Following a TRIP, the status of the signals is frozen signalling the trip (K51/7) and the protection that caused
it.
Note 2: If dip switch no. 10 (RESET) is set to its “MAN” position, the signals may be reset as described in par. 4.2.
Note 3: If dip switch no. 10 (RESET) is set to its “AUT” position, the signals are reset automatically when the trip on
the protection unit is reset (see par. 4.2).
Note 4: Use of the PR010/T test unit interrupts communication with the PR021/K unit, which will signal a
communication error on the local bus by closing the K51/5 contact.
5.9.2.2.
Latch mode (see par. 4.5.2)
Dip-switch no. 11 to be set to its ON position.
Electric
contact
Event that caused closing of the relay
K51/1
L protection alarm or trip (overload)
K51/2
S protection alarm or trip (selective short-circuit)
K51/3
I protection trip (instantaneous short-circuit)
K51/4
G protection alarm or trip (earth fault)
K51/5
Communication problems on the local bus (bus KO)
K51/6
Protection release TRIP alarm
K51/7
Protection release TRIP alarm
K51/8
L function prealarm (overload)
Electric
contact
Event that caused closing of the relay
Selection of dip-switches
no. 2, 3, 4
A = L protection alarm (overload)
dip no. 2 = A
B = L protection trip (overload)
dip no. 2 = B
A = S protection alarm (selective short-circuit)
dip no. 3 = A
B = S protection trip (selective short-circuit)
dip no. 3 = B
K51/3
I protection trip (instantaneous short-circuit)
---
A = G protection alarm (earth fault)
dip no. 4 = A
B = G protection trip (earth fault)
dip no. 4 = B
K51/5
Communication problems on the local bus (bus KO)
---
K51/6
Protection release TRIP alarm
---
K51/7
Protection release TRIP alarm
---
K51/8
L function prealarm (overload)
---
K51/1
K51/4
K51/2