L3016
1SDH000559R0002
18/52
ABB SACE
SACE PR021/K
In the example, the PR021/K has been set as follows:
•
Self-test function disabled
•
K51 configuration = A-A-A-A
•
Master mode
•
Baud rate = 19.2Kb/s
•
Stand-by function not active
•
Manual Reset mode
•
Latch mode disabled
•
Local bus not terminated
Example of dip-switch settings for the PR021/K unit to be connected to the SACE PR112/P release
Note 1: Following a TRIP, the status of the signals is frozen signalling the trip (K51/7) and the protection that caused
it.
Note 2: The signals bearing this marking are not frozen as indicated in Note 1.
Note 3: If dip switch no. 10 (RESET) is set to its “MAN” position, the signals may be reset as described in par. 4.2.
Note 4: If dip switch no. 10 (RESET) is set to its “AUT” position, the signals are reset automatically when the trip on
the protection unit is reset (see par. 4.2).
Note 5: If a trip is caused by a protection function not included in the set of signals (for example, a trip for “protection
G” has occurred but the K51/4 relay was set for the “Function L prealarm” signal), only the K51/7 relay (the
protection release TRIP alarm) will be switched.
5.5.2. Signals
The signals (K51/1...K51/8) for the SACE PR112 protection release may be divided into 2 modes: Normal and Latch. A
description of the signals in these modes is given below.
5.5.2.1.
Normal mode (see par. 4.5.1)
Dip-switch no. 11 to be set to its OFF position.
1 2
3 4
5 6
7
8
9 10 11
12 13
OFF
ON
1
2
3
4
5
6
7
8
9
10
11
12
13
Electric
contact
Event that caused closing of the relay
Selection of dip-switches
no. 2, 3, 4
K51/1
L protection alarm or trip (overload)
---
K51/2
S protection alarm or trip (selective short-circuit)
---
K51/3
I protection trip (instantaneous short-circuit)
---
A = G protection alarm or trip (earth fault)
dip no. 2 = A
B = L function prealarm (overload)
dip no. 2 = B
Communication problems on the local bus (bus KO)
dip no. 3 = A
Internal overtemperature alarm or trip
dip no. 3 = B
K51/6
LC1 load control (Note 2)
---
K51/7
Protection release TRIP alarm
---
K51/8
LC2 load control (Note 2)
---
K51/5
K51/4