Rev.
L0633
Apparatus
SACE PR010/K
Sh. No.
Mod.
Apparecchio
N° Pag.
ÿþþ
ABB SACE
Doc. No.
N° Doc
RH0043.002
Sh. No
N° Pag..
10
/
20
5.4.
SACE PR010/K with SACE PR112 unit
(with last letter of serial number A…E)
5.4.1. Dip-switch settings
N°
Dip-Sw
Description of
dip-switch
0 (Off)
1 (On)
Note
1
Test
Normal
Self-test
For normal functioning mode, set this dip-switch to
OFF.
2
3
4
5
K51
Configuration
-
-
Not used
6
Mode
Slave
Master
Master if PR112/P + PR010/K.
Slave if PR112/PD + PR010/K.
7
Baud Rate
19.2 kbit/s
38.4 kbit/s
Set 19.2 kbit/s
8
State
Normal
Stand-by
For normal functioning mode, set this dip-switch to
OFF
Example of dip-switch settings for connection of PR010/K unit with SACE PR112/P protection unit.
Dip-switch n°
1
2
3
4
5
6
7
8
5.4.2. Signalling
The significance of signals (K51/1…K51/8) for protection unit SACE PR112 is as follows:
Contact
N° Pin on unit
PR010/K
Event which causes closing of relay
K51/1
5
Alarm protection L (overload)
K51/2
6
Alarm protection S (selective short circuit)
K51/3
7
Alarm protection I (instantaneous short circuit)
K51/4
8
Alarm protection G (ground fault)
K51/5
9
Internal Bus communication problem (bus KO)
K51/6
10
Internal overheat alarm (T=85°C)
K51/7
12
CB trip alarm –TRIP–
K51/8
17
Pre-alarm function L (overload)
Off
On