ABB | SACE Emax 2
30 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
Management operations | 4 - Environmental conditions
>690V version circuit-breakers
Insulating protections must be assembled for >690V circuit-breakers as indicated in the figure.
Circuit-breaker Voltage
Version
Fixed protection
Withdrawable protection
E2.2/E9
800V/900V
F
X
-
W
-
-
E2.2/E
1000V/1150V
F
X
-
W
-
X
E4.2/E9
800V/900V
F
X
-
W
-
-
E4.2/E
1000V/1150V
F
X
-
W
-
X
E6.2/E9
800V/900V
F
X
-
W
-
-
E6.2/E
1000V/1150V
F
X
-
W
-
X
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet
for fixed circuit-breakers and in the kit sheet
for withdrawable circuit breakers.
Grounding
The circuit-breakers in fixed version and the fixed part of withdrawable circuit-breakers are equipped with a
screw for the ground connection.
The connection must be implemented by means of a conductor of suitable cross-section according to the
IEC 61439-1 Standard.
Clean and degrease the area around the screw before making the connection.
After assembly of the conductor, tighten the screw with a torque of 2 Nm - 17.7 lb in.
Figure 73
Figure 74