ABB | SACE Emax 2
16 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Ekip Touch protection trip unit | 8 - Hi-Touch protections
8 - Hi-Touch protections
Availability (Performance)
The following is a complete list of the protections (and related parameters) available with all the Ekip Hi-Touch and Ekip G Hi-Touch trip units, in
the Protections and Advanced menus:
Name
Protection against
Threshold
Time
Auxiliary functions
(1) (2)
S2
(3)
Selective short-circuit
X
X
Trip enable, Zone Selectivity, Startup enable, lock
D
(6)
Directional short circuit
X
X
Trip Enable, Directional Zone Selectivity
(4)
, Startup enable,
Locki, Min Angle Direction
UV2
Minimum voltage
X
X
Trip Enable, Lock
OV2
Maximum voltage
X
X
Trip Enable, Lock
UF2
(5)
Minimum frequency
X
X
Trip Enable, Lock
OF2
(5)
Maximum frequency
X
X
Trip Enable, Lock
Set A-B
Double configuration of the
protections
X
X
Default set, Activation event, Activation delay
(1)
Detailed description in the Design Engineer's manual.
(2)
Locking Function available via Ekip Connect.
(3)
For all the UL versions the maximum time allowed by the trip unit is 0.4 seconds. If a higher value is set, the trip unit signals the error and forces
the parameter to 0.4 seconds.
(4)
Directional Zone Selectivity works as an alternative to S and G Zone Selectivity.
(5)
Protection not active for voltages <30V.
(6)
The protection does not detect the direction of fault current for voltages < 5V.
Summary table of Hi-Touch protections
ABB
ANSI
(4)
Threshold
Tolerance threshold
Time
Calculation
formula t
t
(1)
Tolerance t
t
(2)
S2
50 TD
I5 = 0.6...10 In
step = 0.1 In
± 7 % If
≤
6 In
± 10 % If > 6 In
t5 = 0.05...0.8 s
step = 0.01 s
t
t
= t5
The better of the two
values:
± 10 % or ± 40 ms
D
67
I7 Fw/Bw = 0.6...10 In
step = 0.1 In
± 7 % If
≤
6 In
± 10 % If > 6 In
t7 Fw/Bw =
0.1...0.8 s
step = 0.01 s
t
t
= t7
The better of the two
values:
± 10 % or ± 40 ms
UV2
27
U15= 0,05….0,98 Un
step = 0.001 Un
± 2 %
t15 = 0.05…120 s
step = 0.01 s
t
t
= t15
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
OV2
59
U16= 1….1,5 Un
step = 0.001 Un
± 2 %
t16 = 0.05…120 s
step = 0.01 s
t
t
= t16
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
UF2
81L
f17= 0,9….1 fn
step = 0.001 fn
± 1 %
(5)
t17 = 0,06…300 s
step = 0.01 s
t
t
= t17
The better of the two
values:
± 10 % (min=30ms) or ±
40 ms (for a time set < 5 s)
/ ± 100 ms (for a time set
> 5 s)
OF2
81H
f18= 1….1,1 fn
step = 0.001 fn
± 1 %
(5)
t18 = 0,06…300 s
step = 0.01 s
t
t
= t18
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
Continued on the next page