Ekip Bluetooth module
The Ekip Bluetooth allows connection via Bluetooth between the Ekip trip units, and a support (PC, tablet, or
smart phone) with the Ekip Connect software installed (see the previous paragraph).
IMPORTANT: the Ekip Bluetooth module can also be connected to the trip units when
in service.
NOTE:
Ekip Bluetooth only powers the trip unit. Therefore, in order to set and to display
information on any electronic accessories connected to the terminal box, these must be
powered with an Ekip Supply module (see page
).
It draws its power from a rechargeable lithium-polymer battery delivered with the unit. It is connected directly
to the front test connector of the trip unit, and allows a trip unit without auxiliary voltage to be powered.
It is switched on by pressing the power button on the side, and is equipped with two LEDs:
• The first lit in green with the device on and the battery charge, red with the device turned on and low battery.
• The second flashing blue with active Bluetooth communication.
NOTE:
the red flashing LED indicates that the battery is completely drained, an error condition,
or malfunction of the module.
The battery charging is performed by connecting the module to the USB ports of a PC with the supplied
cable. Connection to a PC automatically switches the module on, and charging in progress is indicated by
the flashing green LED, with increasing frequency as the level of charging rises. Completion of charging is
indicated by the green LED on (fixed).
NOTE:
during recharging, the module must be kept energized.
Further information on Ekip Bluetooth is available on the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular in the kit sheet
, and in the Ekip Connect software manual
Ekip T&P module
The Ekip T&P module is part of the Ekip T&P programming and test kit for Ekip trip units, and allows you to:
• Supply the trip unit in the absence of auxiliary voltage.
• Access the information and the pages for programming the trip unit, and activate the test pages with
Ekip Connect software (see page 68).
IMPORTANT: Ekip T&P can also be connected to the trip units when in service. In the
case of connection to trip units in service, it is not possible to perform a trip test.
NOTE:
Ekip T&P only powers the trip unit. Therefore, in order to set and to display information
on any electronic accessories connected to the terminal box, these must be powered with
an Ekip Supply module (see page
It draws its power from the PC, and connects one side directly to the test connector at the front of the trip
unit, and on the other to the USB ports of the PC with the cable supplied.
It turns on after connecting to the PC, and is equipped with two LEDs, a green one indicating that the module
is on, and a yellow one indicating active communication.