Replace faulty or suspect power supply module in the following way:
For single or parallel operation do steps 1, 2 and 4 to13.
For redundant configuration do steps 1 to 14.
1.
Read
Section 2.2.1, Safety Regulations
.
2.
Check that the new module can replace the old.
3.
Switch off the output from the module (only redundant configuration).
4.
Switch off input power to the module.
5.
Disconnect the wires.
6.
Unmount the module by loosening the module locking.
7.
Mount the new module.
8.
Connect the input wires.
9.
Switch on input power to the module.
10. Perform a function test on the new module.
11. Switch off input power to the module.
12. Connect the output wires.
13. Switch on input power to the module.
14. Switch on the output from the module (only redundant configuration).
Содержание S800 I/O
Страница 1: ...S800 I O HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ User s Guide 3BSE 020 923R101...
Страница 10: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH 7DEOH RI RQWHQWV viii 3BSE 020 923R101...
Страница 80: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH KDSWHU QVWDOODWLRQ 70 3BSE 020 923R101...
Страница 102: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH KDSWHU RQILJXUDWLRQ 92 3BSE 020 923R101...
Страница 104: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH KDSWHU 2SHUDWLRQ 94 3BSE 020 923R101...
Страница 114: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH KDSWHU 0DLQWHQDQFH 104 3BSE 020 923R101...
Страница 130: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH SSHQGL 5HIHUHQFHV 120 3BSE 020 923R101 ORFN LDJUDP 7 7 TX RX X1 X2 E O E O...
Страница 146: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH SSHQGL 5HIHUHQFHV 136 3BSE 020 923R101...
Страница 150: ...HQHUDO QIRUPDWLRQ DQG QVWDOODWLRQ 8VHU V XLGH QGH 140 3BSE 020 923R101...