QUICK START GUIDE
Step 5
-
Wire the alarms
The unit provides three optional alarm contact closures via three
pluggable terminal block and also provides a ground terminal
block. See Information Table on sheet 18.
1.
Run the alarm wires through the appropriate strain relief
fitting.
2.
If required, strip the outer jacket to reveal inner jacketed
conductors.
3.
Strip the inner jacket to expose 0.3 inches (7 mm) of bare
conductor
4.
Connect the pairs of the wires to the pluggable terminal
block. See Information Table on sheet 18.
5.
Plug in terminal blocks into the board mounted terminal
block bases
Note: There is no alarm provision for blown fuse or tripped circuit
breaker.
Step 6
-
Wire the AC input
Danger:
Shock Hazard
-
Confirm the AC source is NOT ENERGIZED before making AC connections.
Danger:
Risque d'électrocution
-
Vérifiez que la source CA N'EST PAS SOUS TENSION avant d'effectuer les
connexions CA.
When connecting to AC mains, follow all local and national wiring rules.
Caution:
Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and
cause a short circuit.
Pluggable terminal block
Figure 10 Pluggable terminal block
Figure 11 AC Feed