QUICK START GUIDE
Step 2
-
Ground the unit
There are #10
-
32 studs on 5/8 centers on the lower back of the unit.
Use this location to provide external grounding as required by code
or network standard. 8 AWG minimum recommended ground wire.
Torque each nut to 26 in
-
lbs.
Unit
Grounding
Figure 4 Unit Grounding
2.
Use a slotted screwdriver to loosen the 4 captive screws of
the upper dead
-
front cover, then remove the upper dead
-
front cover.
1.
For field wiring, open the front door as shown.
DOOR
UPPER DEAD
-
FRONT
SCREWS
Figure 6 Upper dead front screws
DC FIELD
WIRING
SECTION
AC FIELD
WIRING
SECTION
Step 3
-
Open the door and remove dead
-
fronts for access to field wiring
AC
CONDUIT
FOR INPUT
Figure 5 AC/DC Field wiring