1MRS751802-MUM
REX 521
95
Protection Relay
Technical Reference Manual, Standard Configurations
Three-phase over voltage protection, low-set stage, 3U>
Start voltage
0.10...1.60 x Un
Operate time
0.05...300.00 s
Operation mode
Not in use
Definite time
A curve
B curve
Time multiplier
0.05...1.00
Measuring mode
Mode 1 (Phase-to-phase voltages / Peak-to-peak meas.)
Mode 2 (Phase-to-phase voltages / Fundam.freq.)
Mode 3 (Phase-to-earth voltages / Fundam.freq.)
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy
±2.5% of the set value with Measuring Mode 3
±1,0% of the set value with Measuring Modes 1 and 2
Start time
Injected voltages > 1.1 x start voltage:
internal time < 42 ms
total time < 50 ms
Reset time
40...1000 ms (depends on the minimum pulse width set
for the trip output)
Reset ratio, typically
0.96
(Depends on the value of the
Oper.
hysteresis
parameter, refer to the manual of the
Three-phase Overvoltage protection function,
1MRS752322-MUM, chapters 2.3.1. and 3.2.4.)
Retardation time
< 50 ms
Operate time accuracy in DT mode
±2% of set value or ±20 ms
Accuracy class index E in inverse-time mode ± 20 ms or the accuracy appearing when the measured
voltage varies ±2.5%
Three-phase over voltage protection, high-set stage, 3U>>
Start voltage
0.10...1.60 x Un
Operate time
0.05...300.00 s
Operation mode
Not in use
Definite time
Measuring mode
Mode 1 (Phase-to-phase voltages / Peak-to-peak meas.)
Mode 2 (Phase-to-phase voltages / Fundam.freq.)
Mode 3 (Phase-to-earth voltages / Fundam.freq.)
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy
±2.5% of the set value with Measuring Mode 3
±1.0% of the set value with Measuring Modes 1 and 2
Start time
Injected voltages > 1.1 x start voltage:
internal time < 42 ms
total time < 50 ms
Reset time
40...1000 ms (depends on the minimum pulse width set
for the trip output)
Reset ratio, typically
0.96
(Depends on the value of the
Oper.
hysteresis
parameter, refer to the manual of the
Three-phase Overvoltage protection function,
1MRS752322-MUM, chapters 2.3.1. and 3.2.4.)
Retardation time
< 50 ms
Operate time accuracy in DT mode
±2% of set value or ±20 ms
Содержание REX 521
Страница 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Страница 2: ......
Страница 12: ...12 ...
Страница 22: ...22 ...
Страница 62: ...62 ...
Страница 72: ...72 ...
Страница 128: ...128 ...
Страница 132: ...132 ...
Страница 172: ...172 ...
Страница 198: ...198 ...
Страница 249: ......