1MRS751802-MUM
REX 521
177
Protection Relay
Technical Reference Manual, Standard Configurations
Fig. 10.1.3.3.-1 Connection diagram for the standard configuration M01 with
breaker status indication and control signals for opening and
closing of the circuit breaker
10.1.4.
Implementations
In the section below a few implementation examples for the standard configuration
M01 are presented.
10.1.4.1.
Basic angle control by digital input
If an external control signal determined from the earthing situation of the network is
available, it can be used for changing the settings for the basic angle of the
directional earth fault protection. The angle can be switched in between 0
°
and –90
°
.
The usage of basic angle control is useful as compensated network is normally set
to 0
°
and an isolated network is set to -90
°
.
CB
REX 521
TRIP circuit breaker
CLOSE circuit breaker
0
1
CB
st
at
u
s
E
Содержание REX 521
Страница 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Страница 2: ......
Страница 12: ...12 ...
Страница 22: ...22 ...
Страница 62: ...62 ...
Страница 72: ...72 ...
Страница 128: ...128 ...
Страница 132: ...132 ...
Страница 172: ...172 ...
Страница 198: ...198 ...
Страница 249: ......