Table 40. Thermal overload protection, two time constants (T2PTTR)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
Current measurement: ±1.5% of the set value or ±0.002
x I
n
(at currents in the range of 0.01...4.00 x I
n
)
Operate time accuracy
1)
±2.0% of the theoretical value or ±0.50 s
1)
Overload current > 1.2 x Operate level temperature
Table 41. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0
o
C
0.1
Max temperature
T2PTTR
0.0...200.0
o
C
0.1
Operate temperature
T2PTTR
80.0...120.0 %
0.1
Weighting factor p
T2PTTR
0.00...1.00
0.01
Short time constant
T2PTTR
6...60000 s
1
Current reference
T2PTTR
0.05...4.00 x I
n
0.01
Operation
T2PTTR
Off
On
-
Table 42. Residual overvoltage protection (ROVPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 1.1 x set
Start value
55 ms
56 ms
58 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1)
Residual voltage before fault = 0.0 x U
n
, f
n
= 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
32
ABB