Table 37. Negative-sequence overvoltage protection (NSPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 x U
n
0.001
Operate delay time
NSPTOV
40...120000 ms
1
Table 38. Frequency protection (FRPFRQ)
Characteristic
Value
Operation accuracy
f>/f<
±10 mHz
df/dt
±100 mHz/s (in range |df/dt| < 5 Hz/s)
± 2.0% of the set value (in range 5 Hz/
s < |df/dt| < 15 Hz/s)
Start time
f>/f<
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
Operate time accuracy
±1.0% of the set value or ±30 ms
Table 39. Frequency protection (FRPFRQ) main settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
1=Freq<
Frequency protection
operation mode
selection
Start value Freq>
0.900...1.200
xFn
0.001
1.050
Frequency start
value overfrequency
Start value Freq<
0.800...1.100
xFn
0.001
0.950
Frequency start
value underfrequency
Start value df/dt
-0.200...0.200
xFn /s
0.005
0.010
Frequency start
value rate of change
Operate Tm Freq
80...200000
ms
10
200
Operate delay time
for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time
for frequency rate of
change
Voltage Protection and Control
1MRS757058 D
REU615
Product version: 4.0
ABB
31