Signals
Table 286:
PULSETIMER Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 287:
PULSETIMER Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
Settings
Table 288:
PULSETIMER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
13.3.1.5
Controllable gate function block GATE
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Controllable gate function block
GATE
-
-
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
Function block
GATE
INPUT
OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 170:
GATE function block
Signals
Table 289:
GATE Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Section 13
1MRK 504 135-UEN A
Logic
382
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...