Table 61. Circuit breaker failure protection (CCBRBRF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Operate time accuracy
±1.0% of the set value or ±20 ms
Retardation time
< 20 ms
Table 62. Circuit breaker failure protection (CCBRBRF) main settings
Parameter
Function
Value (Range)
Step
Current value (Operating phase
current)
CCBRBRF
0.05...1.00 x I
n
0.05
Current value Res (Operating
residual current)
CCBRBRF
0.05...1.00 x I
n
0.05
CB failure mode (Operating mode
of function)
CCBRBRF
1=Current
2=Breaker status
3=Both
-
CB fail trip mode
CCBRBRF
1=Off
2=Without check
3=Current check
-
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
Table 63. Arc protection (ARCSARC)
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 x I
n
Operate time
Minimum
Typical
Maximum
Operation mode = "Light
+current"
1)2)
12 ms
3)
7 ms
4)
14 ms
3)
8 ms
4)
16 ms
3)
11 ms
4)
Operation mode = "Light only"
2)
9 ms
3)
4 ms
4)
10 ms
3)
6 ms
4)
12 ms
3)
6 ms
4)
Reset time
< 40 ms
3)
< 55 ms
4)
Reset ratio
Typical 0.96
1)
Phase start value = 1.0 x I
n
, current before fault = 2.0 x set
Phase start value, f
n
= 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2)
Includes the delay of the heavy-duty output contact
3)
Normal power output
4)
High-speed output