Table 25. Environmental tests
Description
Type test value
Reference
Dry heat test
• 96 h at +55ºC
• 16 h at +85ºC
1)
IEC 60068-2-2
Dry cold test
• 96 h at -25ºC
• 16 h at -40ºC
IEC 60068-2-1
Damp heat test
• 6 cycles (12 h + 12 h) at +25°C…+55°C,
humidity >93%
IEC 60068-2-30
Change of temperature test
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
IEC60068-2-14
Storage test
• 96 h at -40ºC
• 96 h at +85ºC
IEC 60068-2-1
IEC 60068-2-2
1)
For IEDs with an LC communication interface the maximum operating temperature is +70
o
C
Table 26. Product safety
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Table 27. EMC compliance
Description
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
Table 28. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Transformer Protection and Control
1MRS757846 A
RET620
Product version: 2.0
ABB
25
Содержание RET620
Страница 1: ...Relion 620 series Transformer Protection and Control RET620 Product Guide ...