Fig. 5.1.9.5.-1 Linearization curve example
When the linearization for all the necessary RTD1 channels is ready, the tool can be
exited. After exiting, the tool starts to prepare a downloadable linearizing file. This
file can be downloaded to the terminal by using the Relay Download Tool, also
included in the CAP 505 software. In the download tool, the transducer linearization
check box should be checked before the downloading is started.
If the "Store + Reset after download" check box is checked when clicking the Send
button, then the Store and Reset commands are sent automatically after a successful
download of the selected files (see Figure 5.1.9.5.-2).
TLT_send
Fig. 5.1.9.5.-2 Downloading the linearization curve to the transformer terminal