Transformer Terminal
Technical Reference Manual, General
RET 54_
5.1.4.
Parameterization
To ensure that a protection function block protects the transformer in the desired
manner, the default values of parameters are to be checked and properly set before
taking the function block into use.
The parameters can be set either locally over the HMI or externally via the serial
communication.
5.1.4.1.
Local parameterization
When the parameters are set locally via the HMI, the setting parameters can be
chosen from the hierarchical menu structure. The desired language for parameter
description can also be selected. Detailed information about setting and navigation
is found in the RE_ 54_ Operator’s Manual.
5.1.4.2.
External parameterization
The Relay Setting Tool is used for parameterization and setting the RET 54_
transformer terminals externally. The parameters can be set off-line on a PC and
downloaded to the transformer terminal over a communication port. The menu
structure of the setting tool, including views relating to parameterization and
settings, is the same as the menu structure of the transformer terminal. The use of
the tool is instructed in the LIB, CAP, SMS, Tools for Relays and Terminals, User’s
Guide (see “Related documents” on page 9).
RET_Settings
Fig. 5.1.4.2.-1 Main dalog box of the Relay Setting Tool