Settings
Table 79:
MFAPSDE Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Power direction logic Disable
Enable
-
-
Enable
Power direction logic
Peak Counter Limit
3...20
-
-
3
Peak counter limit
for intermittent
(restriking) EF
detection
Operating Quantity
Adaptive
Amplitude
Resistive
-
-
Adaptive
Operating quantity
selection
Voltage Start Value
500...10000
V
1
500
Voltage start value
Operate Delay Time
60...60000
ms
1
500
Operate delay time
Directional Mode
Forward
Reverse
-
-
Forward
Directional mode
Tilt Angle
5...20
Deg
1
10
Characteristics tilt
angle
Reset Delay Time
0...60000
ms
1
500
Reset delay time
Start Delay Time
30...60000
ms
1
30
Start delay time
Min Forward
Operate Current
1.0...20.0
A
0.1
1
Minimum operate
current in forward
direction
Min Reverse
Operate Current
1.0...20.0
A
0.1
1
Minimum operate
current in reverse
direction
Table 80:
MFAPSDE Technical data
Characteristic
Value
Operation accuracy
At frequency f = f
n
±5% in the range of 480 V...9.6 kV
±0.5% in the range of 9.6...28.8 kV
Operate time accuracy
±1.0% of the set value or ±20 mS
6.1.6.6
Voltage presence indication
Voltage presence indication PHSVPR
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage presence indication
PHSVPR
PHSVPR
PHSVPR
1MRS757488 H
Section 6
Commissioning
RIO600
135
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...