relay, PCM600 does not allow writing the configuration to the
device. If other digits in the order code do not match, PCM600
informs about the mismatch with a dialog.
GUID-6EB85C58-4EF4-4672-A3B2-92CB07EAC98A V3 EN
Figure 28:
IED order code selection
4.
On the
Configuration Selection Page
, select the configuration type and click
Next
.
•
Select
Empty configuration
to create an empty configuration.
•
Select
Example configuration
to import any existing example
configuration.
Click
Browse
to select the .pcmi/.pcmt file that has the example
configuration.
•
Select
Standard configuration
to generate a default configuration.
5.
On the
Version Selection page
, select the IEC 61850 version and click
Next
to
generate the functions.
6.
The
Setup Complete Page
shows the summary of the IED type, version, IP
address and the selected order number. Click
Finish
to confirm the
configuration and conduct the insertion.
4.3.3
Inserting an IED from the template directory
IED templates can be used for replicating IEDs with same order code in PCM600
projects. Template includes IED application configuration, graphical display
configuration (single-line diagram), communication protocol mappings and
parameters. An IED in the plant structure can be exported as a template (.pcmt file).
The template library can be built from all the exported IED templates.