![ABB Relion SAM600-IO Скачать руководство пользователя страница 45](http://html.mh-extra.com/html/abb/relion-sam600-io/relion-sam600-io_protocol-manual_2831045.webp)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Loc
v1_dSPS
t
ST
-
LOC
Mon
Timestamp: Local operation
allowed
Rem
v1_dSPS
stVal
ST
-
REM
Mon
Remote operation allowed
q
ST
-
REM
Mon
Quality: Remote operation
allowed
t
ST
-
REM
Mon
Timestamp: Remote operation
allowed
7.2.2
Switch controller CSWI
7.2.2.1
Switch controller SCSWI
GUID-4F40A4BA-6781-41BF-8389-D8EFD791D005 v1
PID-3955-LOGICALNODEDATA v1
LN type
LN prefix LN class Function block name
SCSWI (revision 1) S
CSWI
SCSWI
Table 3:
SCSWI Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Pos
a_dDPC
Cancel.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
Cancel.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
SBOw.ctlVal
CO
-
-
Cmd
Command parameter for
IEC61850
SBOw.origin.orCat
CO
-
-
Cmd
Command parameter for
IEC61850
SBOw.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Cancel.origin.orIdent
CO
-
-
Cmd
Command parameter for
IEC61850
Cancel.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
Oper.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
SBOw.ctlNum
CO
-
-
Cmd
Command parameter for
IEC61850
SBOw.T
CO
-
-
Cmd
Command parameter for
IEC61850
Table continues on next page
1MRK 511 440-UEN A
Section 7
Logical node data model
Switchgear control unit SAM600-IO Version 2.2 IEC
39
Communication protocol manual