It does NOT however allow the User to define the substation
part.
IET600:
•
Open a SCD file or import/merge a SCD, ICD or CID file for the particular
IED(s).
•
For each IED, the user defines the datasets, the control blocks for reporting
(this means unbuffered/buffered reporting and GOOSE) and the properties for
each report control block.
Data sets (DS) are generated automatically in PCM600. Report
control blocks (RCBs) are automatically created in PCM600
only when using templates.
•
If client definitions (like client. ICD) are required in the system configuration,
they are merged into IET600 and connected to the unbuffered/buffered report
control blocks.
•
Logical nodes, which are not related to the conducting equipment, must be
included in the bay level in the substation section.
•
The resulting SCD file is exported from IET600.
•
Define the inputs for the client in IET600 and cross-reference the signals in
SMT.
If input signals are not defined for clients in IET600, they will not
be visible in SMT. Inputs (GOOSE clients) can also be defined in
PCM600.
PCM600:
Import the SCD file to PCM600 to receive GOOSE data. For each IED that shall
receive GOOSE information, the received data is connected to the applications
using SMT in PCM600. To be able to import scd-file to PCM600, 61850
engineering mode in PCM must be disabled.
3.5
Engineering concept in IEC 61850-6
GUID-FFE87459-FBC1-4D85-A6B3-7BD6F576ECE4 v3
•
Top-down approach means that the system engineering tool has ICD files
available for each IED to be included in the system configuration. The ICD
files may be of the template type and represent a pre-configured IED.
•
Bottom-up approach means that the configurations are produced by the IED
tool, and that are exported as CID files (or SCD file) to be imported into the
system tools.
1MRK 511 440-UEN A
Section 3
Substation Configuration description Language (SCL)
Switchgear control unit SAM600-IO Version 2.2 IEC
21
Communication protocol manual