α
Lead
BusA
f
s
TCB ds
dt
TCB
=
⋅
⋅
+
⋅
⋅
360
2
1000
1000
(Equation 372)
f
BusA
Bus A side frequency
s
Frequency slip
ds/dt
Frequency slip acceleration
TCB
Setting
Closing time of CB
The breaker closes only when the measured phase-angle difference across
the breaker (PH_DIFF_MEAS) equals the calculated lead angle (α
Lead
) and all
synchronization check conditions are fulfilled.
If
Synchrocheck mode is set to "Synchronous", a zero-passage of the
phase-angle difference is not necessary and CB closing is permitted as
soon as all the synchrocheck conditions are fulfilled. Similarly for dead
bus synchronization, CB closing is possible when the energizing check
permits.
The CB closing signal can be blocked based on the inputs
CB_TEST
and
EXT_CHECK
and IED test mode as described in
. This blocking status is available in the
monitored data CB_CL_BLKD.
Table 1532: CB_CL_BLKD status based on the inputs
IED test mode
Inputs
Monitored data
CB_TEST
EXT_CHECK
CB_CL_BLKD
TRUE
TRUE
TRUE
1 (“Unblocked”)
FALSE
FALSE
TRUE
TRUE
FALSE
2 (“Ext Check Fail”)
FALSE
FALSE
TRUE
FALSE
N/A
3 (“IED Test CB Serv-
ice”)
FALSE
TRUE
N/A
4 (“IED Service CB
Test”)
ASNSCSYN can be set to the bypass mode by setting the parameters
Synchrocheck
mode and Live dead mode to "Off" or, alternatively, by activating the
BYPASS
input.
In the bypass mode, the closing conditions are always considered to be fulfilled by
ASNSCSYN.
Synchronization control
The general bus bar arrangement for a non-source CB bus is shown in
. The bus to which the generator is connected is determined based on the
circuit breaker and isolator position inputs (
CB_OPEN
,
CB_CLOSE
,
ISO_A1_CLOSE
,
ISO_A2_CLOSE
,
ISO_B1_CLOSE
and
ISO_B2_CLOSE
). The generator's bus
connection status is shared with ASCGAPCs as part of the
NS_ASC_DATA
output.
1MRS759142 F
Control functions
REX640
Technical Manual
1595
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......