The equipment which is capable of voltage and frequency adjustment,
that is, the generator, is referred to as source and the rest as nonsource.
Hence the generator's CB is referred to as source CB and the bus coupler
or tie feeder CB as non-source CB. The non-source CB is not directly
related to a generator although its closing has to be handled using
synchronization.
Bus A2
Non Source CB
Bus A1
Bus A2
Non Source CB
Bus B2
Bus A1
Bus B1
Single busbar arrangement
Double busbar arrangement
ISO A1
ISO B1
ISO A2
ISO B2
ISO A1
ISO A2
Figure 873: Different busbar arrangement for a non-source CB
Auto synchronization mode
In this mode, the closing signal is delivered if either the command
Synchronize CB
or the input
CL_COMMAND
is set to TRUE. The device should be in local mode if
synchronization is initiated with the
Synchronize CB command.
If the setting
Auto Syn mode is set as "Manual mode" or "Semi-automatic
synchronising mode", the additional command Manual CB release should be active
for the closing signal
CLOSE_CB
to be activated. If the setting
Auto Syn mode is set
as "Automatic synchronising mode", no additional command is required to activate
the closing signal
CLOSE_CB
.
In this auto synchronization mode, once all the closing conditions are satisfied
within the set
Maximum Syn time, the outputs
SYNC_OK
and
CLOSE_CB
become
TRUE and remain active as long as the closing conditions are fulfilled. If
Multiple
command is set to "Off", then only
CLOSE_CB
outputs are delivered once for
each activated input signal as shown in
Multiple command is set to
"On", then
CLOSE_CB
outputs are delivered each time the conditions are satisfied
as shown in
. In this auto synchronization mode, once all the closing
conditions are satisfied within the set
Maximum Syn time, the outputs
SYNC_OK
and
CLOSE_CB
become TRUE. These outputs remain active as long as the respective
conditions are fulfilled. If
Multiple command is set to "Off", then only
CLOSE_CB
outputs are delivered only once for each activated input signal as shown in
. If
Multiple command is set to "On", then
CLOSE_CB
outputs are delivered each
time the conditions are satisfied as shown in
Control functions
1MRS759142 F
1596
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......