There are OUT signals under the Single command menu.
Selector switch SLGGIO
Main menu/Test/Function status/Control/Commands/SelectorSwitch(GGIO)/
SLGGIO:x
An application dependent number of switches can be displayed here. The position
of each switch is indicated here. There are up to a number of possible switch
positions. The number of switches and switch positions is determined by the
configuration in the PCM configuration tool.
Selector mini switch VSGGIO
Main menu/Test/Function status/Control/Commands/VersatileSwitch/
VSGGIO:x
Displays the output data of the VSGGIO function.
11.6.10.3
IEC61850 generic communication I/O functions DPGGIO
Main menu/Test/Function status/Control/DoubelPointIndication(DPGGIO)/
DPGGIO:x
Displays the output data of the DPGGIO function.
11.6.10.4
Synchrocheck and energizing check SESRSYN
Main menu/Test/Function status/Control/Synchronizing(RSYN,25)/
SESRSYN:x
Displays available instances of SESRSYN with a number of measurements per
instance. These include information about which lines and buses selected, various
voltage and frequency differences and feedback on synchronization status.
11.6.10.5
Tap changer control and supervision TCMYLTC/TCLYLTC
Main menu/Test/Function status/Control/TransformerTapControl(YLTC,84)/
TCMYLTC:x
Main menuTestFunction statusControlTransformerTapControl(YLTC,
84)TCLYLTC:x
Displays data about available instances of tap changer parameters such as tap
positions for low and high voltage and type of code conversion.
Section 11
1MRK504114-UEN E
Test the IED
92
Operator's manual
Содержание RELION RET670
Страница 1: ...Relion 670 series Transformer protection RET670 Operator s manual...
Страница 2: ......
Страница 22: ...16...
Страница 26: ...20...
Страница 34: ...28...
Страница 42: ...36...
Страница 44: ...38...
Страница 76: ...70...
Страница 108: ...102...
Страница 112: ...106...
Страница 118: ...112...
Страница 127: ...121...