Table 51. General current and voltage protection (GAPC), continued
Function
Range or value
Accuracy
Voltage level where voltage
memory takes over
(0.0 - 5.0)% of U
base
± 1.0% of U
r
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of U
base
± 1.0% of U
r
for U<U
r
± 1.0% of U for U>U
r
Start undervoltage, step 1
and 2
(2.0 - 150.0)% of U
base
± 1.0% of U
r
for U<U
r
± 1.0% of U for U>U
r
Operate time, start
overvoltage
25 ms typically at 0 to 2 x U
set
-
Reset time, start overvoltage
25 ms typically at 2 to 0 x U
set
-
Operate time start
undervoltage
25 ms typically 2 to 0 x U
set
-
Reset time start undervoltage
25 ms typically at 0 to 2 x U
set
-
High and low voltage limit,
voltage dependent operation
(1.0 - 200.0)% of U
base
± 1.0% of U
r
for U<U
r
± 1.0% of U for U>U
r
Directional function
Settable: NonDir, forward and
reverse
-
Relay characteristic angle
(-180 to +180) degrees
± 2.0 degrees
Relay operate angle
(1 to 90) degrees
± 2.0 degrees
Reset ratio, overcurrent
> 95%
-
Reset ratio, undercurrent
< 105%
-
Reset ratio, overvoltage
> 95%
-
Reset ratio, undervoltage
< 105%
-
Overcurrent:
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Undercurrent:
Critical impulse time
10 ms typically at 2 to 0 x I
set
-
Impulse margin time
15 ms typically
-
Overvoltage:
Critical impulse time
10 ms typically at 0 to 2 x U
set
-
Impulse margin time
15 ms typically
-
Transformer protection RET670
1MRK 504 091-BEN B
Pre-configured
Product version: 1.1
Issued: June 2010