Differential protection
Table 23. Transformer differential protection T2WPDIF, T3WPDIF
Function
Range or value
Accuracy
Operating characteristic
Adaptable
± 2.0% of Ir for I < Ir
± 2.0% of Ir for I > Ir
Reset ratio
> 95%
-
Unrestrained differential current
limit
(100-5000)% of
IBase on high
voltage winding
± 2.0% of set value
Base sensitivity function
(10-60)% of IBase
± 2.0% of Ir
Second harmonic blocking
(5.0-100.0)% of
fundamental
± 2.0% of Ir
Fifth harmonic blocking
(5.0-100.0)% of
fundamental
± 5.0% of Ir
Connection type for each of the
windings
Y or D
-
Phase displacement between high
voltage winding, W1 and each of
the windings, W2 and W3. Hour
notation
0–11
-
Operate time, restrained function
25 ms typically at
0 to 2 x Id
-
Reset time, restrained function
20 ms typically at
2 to 0 x Id
-
Operate time, unrestrained
function
12 ms typically at
0 to 5 x Id
-
Reset time, unrestrained function
25 ms typically at
5 to 0 x Id
-
Critical impulse time
2 ms typically at 0
to 5 x Id
-
Transformer protection RET670
1MRK 504 091-BEN B
Pre-configured
Product version: 1.1
Issued: June 2010
ABB
51