IEEE 1344. IEEE 1344 can provide Time Zone offset (TZ) as an additional
information. Encoded IRIG-B time plus TZ (Time Zone) offset always equals to
UTC.
TimeZoneAs1344
: This parameter is used to specify the sign of Time Zone (TZ)
offset as defined in IEEE 1344 and according to the external clock. The options are
"Plus TZ" or "Minus TZ". Encoded IRIG-B time plus Time Zone offset always
equals to UTC.
IEEE 1588 (PTP)
GUID-424227EC-74A1-4628-8948-C1876840ABFE v3
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration
tool /ECT) in PCM600.
PTP
can be set to
On
,
Off
or
Slave only
. When set to
Slave only
the IED is
connected to the PTP-group and will synchronize to the grandmaster but cannot
function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To
set one IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089-1-en.vsdx
IEC16000089 V1 EN-US
Figure 122:
Enabling PTP in ECT
The
PTP VLAN
tag must have the same value in station clock and in the IED. The
default value is set to 0.
The
PTP VLAN
tag does not need to be the same on all access points in one IED. It
is possible to mix as long as they are the same for all devices on each subnet.
Section 22
1MRK 511 407-UEN C
Basic IED functions
352
Phasor measurement unit RES670 2.2 IEC
Application manual
Содержание Relion RES670
Страница 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 46: ...40...
Страница 52: ...46...
Страница 92: ...86...
Страница 112: ...106...
Страница 178: ...172...
Страница 216: ...210...
Страница 232: ...226...
Страница 286: ...280...
Страница 328: ...322...
Страница 340: ...334...
Страница 380: ...374...
Страница 381: ...375...