individual function. One of the submenus shows the status of the LEDs on the
HMI.

10. Communication displays submenus and Station communication.

All measurement descriptions in this document reflect the maximum number of
hardware units possible in any application. In reality the hardware in the IED will
be chosen according to a particular application. For example, it is possible to equip
a 1/1 x 19” case IED with 14 I/O modules. In reality fewer I/O modules may be
installed. In the measurements menu the operator will only see data from the
hardware and software installed.

11.2 

IED test mode

Main menu/Test/IED test mode

Displays a setting which is used to activate and deactivate functions so that tests
can be performed without endangering system stability and a setting with which
events can be enabled or disabled.

11.3 

View binary input values

11.3.1 

Overview

Binary input values display the state of each individual input in the Binary input
modules (BIM). These are indicated with a 1 or 0 depending on whether a signal is
present or not. Binary input modules with enhanced pulse counting capabilities can
receive pulses used for power measurement. The number of pulses received is used
to measure power.

11.3.1.1 

Binary Input Module BIM

Main menu/Test/Binary input values/Binary input modules

Displays available binary input modules with several binary values per module.

11.3.1.2 

Signal matrix for binary input SMBI

Main menu/Test/Binary Input Values/SMT binary inputs/Instance:x

Displays available instances of SMT binary inputs with several inputs per instance.

Section 11

1MRK511251-UEN B

Test the IED

54

Operator's manual

Содержание Relion RES670

Страница 1: ...Relion 670 series Phasor measurement unit RES670 Operator s manual...

Страница 2: ......

Страница 3: ...Document ID 1MRK511251 UEN Issued February 2015 Revision B Product version 1 2 Copyright 2012 ABB All rights reserved...

Страница 4: ...or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be...

Страница 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Страница 6: ...rning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN...

Страница 7: ...tify the IED 15 Section 4 Understand the IED local human machine interface 19 Overview 19 Keypad 19 Key activated screens 21 The Help screen 21 The Reset screen 21 LCD 21 Medium 21 LED 22 Introduction...

Страница 8: ...ts 31 Overview 31 Section 8 Handle disturbances 33 Identify a disturbance 33 View disturbance record details 33 View general information 33 View disturbance indications 33 View event recordings 33 Vie...

Страница 9: ...s VMSQI 43 Disturbance report DRPRDRE 43 Fault locator LMBRFLO 44 Generic measured value MVGGIO 44 Event function 44 Logical signal status report BINSTATREP 44 Metering 44 Overview 44 Pulse counter lo...

Страница 10: ...use failure supervision SDDRFUF 48 Monitoring 48 Overview 48 Event counter CNTGGIO 49 Fault locator LMBRFLO 49 Logic 49 Overview 49 Tripping logic SMPPTRC 49 Trip matrix logic TMAGGIO 49 LogicGate 49...

Страница 11: ...tep undervoltage protection UV2PTUV 58 Frequency protection 58 Overfrequency protection SAPTOF 58 Rate of change frequency protection SAPFRC 58 Underfrequency protection SAPTUF 58 Multipurpose protect...

Страница 12: ...67 Overview 67 Read measured values and check apparatus status 67 Locating and using the single line diagram 67 Control screen messages 69 Section 13 Reset 71 Reset guide for IED 71 Reset counters 71...

Страница 13: ...Section 15 Glossary 79 Table of contents 7 Operator s manual...

Страница 14: ...8...

Страница 15: ...eringmanual Commissioning manual manual Technical reference IEC09000744 V1 EN The Application Manual AM contains application descriptions setting guidelines and setting parameters sorted per function...

Страница 16: ...recommends a sequence for engineering of protection and control functions LHMI functions as well as communication engineering for IEC 61850 and DNP3 1 1 2 About the operator s manual Use the operator...

Страница 17: ...s kind of equipment 1 1 4 Related documents Documents related to RES670 Identity number Operator s manual 1MRK 511 251 UEN Installation and commissioning manual 1MRK 511 252 UEN Technical reference ma...

Страница 18: ...vision notes Revision Description First issue for 670 series version 1 2 A Maintenance updates PR corrections B Maintenance updates PR corrections Section 1 1MRK511251 UEN B Introduction 12 Operator s...

Страница 19: ...site configuration Operating the IED without proper earthing may damage both IED and measuring circuitry and may cause injuries in the event of an accident Never remove any screw from a powered IED or...

Страница 20: ...14...

Страница 21: ...eference For example the fault currents and voltages at the time of the fault can be documented The operator can also retrieve data about protected objects providing further information for fault anal...

Страница 22: ...ries product type REB REC RED REG REL RET and so on ProductDef specifies the version of the product in the following order major version minor version major revision minor revision 1 2 2 0 for example...

Страница 23: ...IEDMainFunType Specifies the main IED functionality in accordance to IEC60870 5 103 numbering REL 128 compatible range REC 242 private range RED 192 compatible range RET 176 compatible range REB 207 p...

Страница 24: ...18...

Страница 25: ...he human machine interface is used to monitor and to some extent control the way the IED operates The configuration designer can add functions that alert to events requiring the attention of the opera...

Страница 26: ...00104 V1 EN Press to clear entries cancel commands or edit IEC05000105 V1 EN Press to open the main menu and to move to the default screen IEC05000106 V1 EN Press to set the IED in local or remote con...

Страница 27: ...and close ON breakers and disconnectors when using the Single Line Diagram SLD in direct control situations 4 3 2 The Reset screen The reset screen is activated by the Reset key on the front panel of...

Страница 28: ...riggered Flashing Terminal in test mode Red Steady Trip command issued 4 5 3 Indication LEDs The LED indication module comprising 15 LEDs is standard in 670 series Its main purpose is to present an im...

Страница 29: ...MI Screen 4 7 How to navigate 4 7 1 Read To read values and access information about the objects being monitored the operator must navigate the menu tree using the arrow keys The active submenu or val...

Страница 30: ...row keys to change the digit or letter concerned 5 Press the E key once the desired changes have been made 6 Press the left arrow key to move up a level in the HMI tree 7 You will be prompted to confi...

Страница 31: ...Report Settings Diagnostics Test and Reset These branch out into a typical tree structure 5 1 Overview The local HMI has the following main menu Control Measurements Events Disturbance records Settin...

Страница 32: ...26...

Страница 33: ...side of the current transformers CTs 2 Analog secondary values are the quantities measured on the secondary side of the current and voltage transformers These are the quantities measured on the Trans...

Страница 34: ...shown here 6 4 1 1 mA input module MIM Main menu Measurements Analog mean values mA modules MIM x Displays input data from the milli ampere module which has six inputs Each input has a range of 20 mA...

Страница 35: ...urrent values for a three phase line both magnitude and phase angle for each component are displayed These indicate how well balanced a system is In an ideal balanced system the zero sequence current...

Страница 36: ...Function for energy calculation and demand handling ETPMMTR Main menu Measurements Metering ThreePhEnergMeas MMTR ETPMMTR x The output data generated from the energy measuring function includes active...

Страница 37: ...ew events 7 1 1 Overview Events displays recorded events such as trips and breaker opened or closed Main menu Events Displays a list of events in chronological order and where each event has a time st...

Страница 38: ...32...

Страница 39: ...escribed in the sections that follow 8 2 View disturbance record details 8 2 1 View general information By choosing General information after selecting a disturbance record in the list of disturbance...

Страница 40: ...splayed The path in the HMI is shown below Main menu Disturbance records Record xx Trip Values 8 3 Trigger a disturbance report manually Using the manual trigger generates an instant disturbance repor...

Страница 41: ...ust not be turned off Do not perform a setting change at the same time as a hardware reconfiguration Doing so might cause the IED to malfunction 9 1 System time and synchronization 9 1 1 System time M...

Страница 42: ...aylight Savings Time is set here 9 1 2 6 SYNCHIRIG B Main menu Settings Time Synchronization SYNCHIRIG B x The type of input time domain type of encoding and time zone for IRIG B are set here 9 1 2 7...

Страница 43: ...ettings Power system Primary values Displays the system frequency 9 2 2 Communication 9 2 2 1 Overview The parameter settings for communications are found under General Settings Communications Communi...

Страница 44: ...operation The mode of operation is either steady or pulsed Configuration parameters for IEEE1344 and C37 118 protocol PMUCONF Main Menu Settings General settings Communication Station communication P...

Страница 45: ...rimary and secondary values from the measuring transformers The channel type and ratings are shown but cannot be changed The settings for binary inputs and outputs even include the milliampere input m...

Страница 46: ...reen Functions Reference channel service values and the Change lock function In the LED submenu there are settings for operation illumination times and sequence types for the LEDs on the IED front pan...

Страница 47: ...of the bay control function QCBAY with a setting that gives the local operator priority over the remote operator or vice versa Local Remote switch LocalRemote LocRemControl Main menu Settings General...

Страница 48: ...and the Measured value expander block 9 2 6 2 Service values CVMMXN Main menu Settings General Settings Monitoring ServiceValues MMXN CVMMXN x Displays available instances of CVMMXN 9 2 6 3 Current p...

Страница 49: ...oltage sequence components VMSQI Main menu Settings General settings Monitoring VoltageSequenceComponents MSQI VMSQI x The voltage sequence components are where the user sets the limits and deadband s...

Страница 50: ...unction block and to set the threshold values This is a generic function and therefore the input values depend on the application 9 2 6 10 Event function Main menu Settings General settings Monitoring...

Страница 51: ...for accumulated energy values are found here 9 3 Setting group N 9 3 1 Overview There are some default setting groups Under general settings parameters in these groups can be changed to suit the needs...

Страница 52: ...n SensDirResOvCurr PSDE 67N SDEPSDE x Includes voltage current operation mode and timer settings 9 3 3 Voltage protection 9 3 3 1 Overview For Voltage protection there are settings for Under voltage O...

Страница 53: ...the Operation setting must be On 9 3 4 3 Rate of change frequency protection SAPFRC Main menu Settings Setting Group N Frequency protection RateOfChangeOfFrequency PFRC 81 SAPFRC x Displays available...

Страница 54: ...ated current and operation There are six instances of Fuse failure supervision parameters for setting rated current voltage operation mode and several other parameters 9 3 6 2 Current circuit supervis...

Страница 55: ...3 8 Logic 9 3 8 1 Overview Under Logic there are settings for Trip logic Trip matrix Logic gate Logic SR memory and Logic timer set Under each of these function categories there are a number of instan...

Страница 56: ...Main menu Settings Setting group N Logic LogicSRMemory SRMEMORY x Displays setting parameters for operating mode of memory function 9 3 8 7 LogicTimerSet Main menu Settings Setting Group N Logic Logi...

Страница 57: ...e status of each item on the list To identify the type of IED you are confronted with navigate to identifiers using the keypad The path to identity parameters is shown below Main menu Diagnostics IED...

Страница 58: ...Communication Rear OEM port CD Displays various communication status signals for rear CD port communication Main menu Diagnostics Communication Redundant PRP Displays communication status for redunda...

Страница 59: ...easurement 3 Current protection displays a choice of functions To view data related to these functions it is necessary to choose one from the list and navigate to the screen for the function in questi...

Страница 60: ...formed without endangering system stability and a setting with which events can be enabled or disabled 11 3 View binary input values 11 3 1 Overview Binary input values display the state of each indiv...

Страница 61: ...ignal matrix for binary outputs SMBO Main menu Test Binary output values SMT binary outputs Displays available sets of binary output values Each set or instance of binary outputs displays the status o...

Страница 62: ...lure supervision 11 5 7 Control Main menu Test Function test modes Control Test of synchrocheck and energizing check function 11 5 8 Monitoring Main menu Test Function test modes Monitoring Test of mo...

Страница 63: ...Displays available instances of EF4PTOC with a number of measurements per instance The measurements indicate trip and start signal status as well as the 2nd harmonic block signal status 11 6 1 4 Sens...

Страница 64: ...2 Rate of change frequency protection SAPFRC Main menu Test Function status Frequency protection RateOfChangeOfFrequency PFRC SAPFRC x Displays available instances of SAPFRC with measurement data for...

Страница 65: ...gether with various start and current data 11 6 5 1 Current circuit supervision CCSRDIF Main menu Test Function status Secondary system supervision CurrentCircuitSupervision RDIF 87 CCSRDIF x Displays...

Страница 66: ...position of each switch is indicated here There are up to a number of possible switch positions The number of switches and switch positions is determined by the configuration in the PCM configuration...

Страница 67: ...tory The maximum number of incoming analog channels is 40 and their Trig status is indicated here The Fault number parameter generates an integer indicating the number of faults recorded since the las...

Страница 68: ...asValExpander RANGE_XP x Displays available instances of the function block RANGE_XP These show the boolean values assigned to the integer values generated by analog inputs 11 6 7 10 IEC61850 generic...

Страница 69: ...nstances of the function TMAGGIO with some boolean output values per instance The output signals from this function block are typically connected to other logic blocks or directly to IED output contac...

Страница 70: ...Station communication MultipleCommandReceive MULTICMDRCV x The MultiCommand Receive indications displayed here show available sets of output data Each set of output data has a number of signals Other...

Страница 71: ...vated by a binary input and the SETTING parameter indicates whether or not test mode has been activated by a setting The output data is binary 0 or 1 11 6 12 Authorization Main menu Test Function stat...

Страница 72: ...66...

Страница 73: ...on of a rotating switch It is only visible if it has been configured in the PCM600 12 1 1 Read measured values and check apparatus status In the single line diagram a number of measured quantities are...

Страница 74: ...05000235 vsd IEC05000235 V1 EN Earth xx05000236 vsd IEC05000236 V1 EN Feeder system xx05000237 vsd IEC05000237 V1 EN Generator xx05000238 vsd IEC05000238 V1 EN Disconnector xx05000240 vsd IEC05000240...

Страница 75: ...at the bottom of the SLD screen and are in the form of a prompt asking the user to confirm an action such as the opening of a circuit breaker They can also warn the user as to conditions that are a hi...

Страница 76: ...70...

Страница 77: ...MI tree Main menu Reset Reset counters PulseCounter GGIO PCGGIO x In the dialog box that appears choose YES to reset 13 1 1 3 Function for energy calculation and demand handling ETPMMTR Main menuReset...

Страница 78: ...oose YES to reset 13 1 3 2 All indication LEDs Activating the Reset of indication LEDs will zero all fifteen LEDs to the right of the LCD Main mnenu Reset Reset LEDs All indication LEDs In the dialog...

Страница 79: ...both access points to the IED local through the local HMI remote through the communication ports 14 2 Principle of operation There are different levels or types of users that can access or operate dif...

Страница 80: ...nfiguration possibilities application configuration including SMT GDE and CMT R R W R R R R W R W File loading database loading from XML file R W R W R W File dumping database dumping to XML file R W...

Страница 81: ...e or more users created with the IED User Management and downloaded into the IED then when a user intentionally attempts a Log on or when the user attempts to perform an operation that is password pro...

Страница 82: ...sed IEEE 1344 Control of phasor data over IEEE 1344 4712 TCP closed IEEE C37 112 Control of phasor data over IEEE C37 112 4713 TCP closed UDP Phasors Control of phasor data over UDP The 670 series sup...

Страница 83: ...be changed The Internet Protocol ports used for phasor data are configurable The default TCP ports 4711 4712 and 4713 can be changed by the user These security drawbacks are acceptable in limited loca...

Страница 84: ...78...

Страница 85: ...r ZD ArgDir Setting parameter ZD ASCT Auxiliary summation current transformer ASD Adaptive signal detection AWG American Wire Gauge standard BBP Busbar protection BFP Breaker failure protection BI Bin...

Страница 86: ...60255 24 Contra directional Way of transmitting G 703 over a balanced line Involves four twisted pairs two of which are used for transmitting data in both directions and two for transmitting clock sig...

Страница 87: ...X 512 515 Access multiplexer FOX 6Plus Compact time division multiplexer for the transmission of up to seven duplex channels of digital data over optical fibers G 703 Electrical and functional descrip...

Страница 88: ...s from the PCI SIG Special Interest Group for the electrical EMF Electromotive force IEEE 1686 Standard for Substation Intelligent Electronic Devices IEDs Cyber Security Capabilities IED Intelligent e...

Страница 89: ...ne carrier module MIM Milli ampere module MPM Main processing module MVB Multifunction vehicle bus Standardized serial bus originally developed for use in trains NCC National Control Centre NUM Numeri...

Страница 90: ...lts RISC Reduced instruction set computer RMS value Root mean square value RS422 A balanced serial interface for the transmission of digital data in point to point connections RS485 Serial link accord...

Страница 91: ...work layer and transport layer protocols While TCP and IP specify two protocols at specific protocol layers TCP IP is often used to refer to the entire US Department of Defense protocol suite based up...

Страница 92: ...alendar It is used for aeroplane and ship navigation where it is also sometimes known by the military name Zulu time Zulu in the phonetic alphabet stands for Z which stands for longitude zero UV Under...

Страница 93: ...87...

Страница 94: ...act us ABB AB Substation Automation Products SE 721 59 V ster s Sweden Phone 46 0 21 32 50 00 Fax 46 0 21 14 69 18 www abb com substationautomation 1MRK511251 UEN B Copyright 2012 ABB All rights reser...

Отзывы: