Table 99:
Supported ASDU types in monitoring direction
Object
type
Description
IEC 60870-5-101/104 ASDU alternatives
Interrogated
Change event
ASDU
Type string
ASDU
Type string
30
Integrated totals 15
M_IT_NA_1
16
M_IT_TA_1
1)
37
M_IT_TB_1
2)
1) Requires setting parameter
Time Format to be in mode “Short 24 bits”
2) Requires setting parameter
Time Format to be in mode “Full 56 bits”
2.5.2
CTRL.CBCSWI1 Operation counter
Table 100:
CTRL.CBCSWI1 Operation counter
Object type Addr
IEC 61850 name
SA name
Description
Values
CTRL.CBSWI1
30
.OpCntRs.stVal
CB1 op. counter
0…65535
2.5.3
LD0.PEMMTR1 Three-phase energy values (1)
Table 101:
LD0.PEMMTR1 Three-phase energy values (1)
Object type Addr
IEC 61850 name
SA name
Description
Values
LD0.PEMMTR1
30
14000
.SupWh.actVal
Reverse active energy
0...1E10 [Kwh]
30
14001
.SupVArh.actVal
Reverse reactive energy
0...1E10 [kVAr]
30
14002
.DmdWh.actVal
Forward active energy
0...1E10 [Kwh]
30
14003
.DmdVArh.actVal
Forward reactive energy
0...1E10 [kVAr]
2.6
Controls
2.6.1
Supported ASDU types
The Object type column contains an internal type identification for the data objects.
The internal object types appear in the protocol as standard IEC 60870-5-101/104
ASDU data types.
Table 102:
Supported ASDU types in control direction
Object type
Description
ASDU
Type string
50
Single bit control
45
C_SC_NA_1
51
Double bit control
47
C_DC_NA_1
Section 2
1MRS757824 C
IEC 60850-5-101/104 data mappings
46
Recloser Protection and Control RER615