2.3.35
LD0.NSPTOV1 Negative-sequence overvoltage protection
(1)
Table 37:
LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
Object type Addr
IEC 61850 name
SA name
Description
Values
LD0.NSPTOV1
1
966
.Str.general
START
General start
1=Start
1
965
.Op.general
OPERATE
General operate
1=Operate
2.3.36
LD0.FRPFRQ1 Frequency protection (1)
Table 38:
LD0.FRPFRQ1 Frequency protection (1)
Object type Addr
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC1
1
889
.Str.general
START
Stage 1 start
1=Start
1
LD0.FRPTOF1
Overfrequency
1
883
.Op.general
OPR_OFRQ
operate
1=Operate
1
LD0.FRPTUF1
Underfrequency
1
895
.Op.general
OPR_UFRQ
operate
1=Operate
1
LD0.FRPFRC2
Frequency gradient
1
877
.Op.general
OPR_FRG
operate
1=Operate
2.3.37
LD0.FRPFRQ2 Frequency protection (2)
Table 39:
LD0.FRPFRQ2 Frequency protection (2)
Object type Addr
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC2
1
890
.Str.general
START
Stage 2 start
1=Start
1
LD0.FRPTOF2
Overfrequency
1
884
.Op.general
OPR_OFRQ
operate
1=Operate
1
LD0.FRPTUF2
Underfrequency
1
896
.Op.general
OPR_UFRQ
operate
1=Operate
1
LD0.FRPFRC2
Frequency gradient
1
878
.Op.general
OPR_FRG
operate
1=Operate
Section 2
1MRS757824 C
IEC 60850-5-101/104 data mappings
26
Recloser Protection and Control RER615
Point List Manual