Table 56. Arc protection (ARCSARC) main settings
Parameter
Function
Value (Range)
Step
Phase start value
(Operating phase
current)
ARCSARC
0.50...40.00 x I
n
0.01
Ground start value
(Operating residual
current)
ARCSARC
0.05...8.00 x I
n
0.01
Operation mode
ARCSARC
1=Light+current
2=Light only
3=BI controlled
Table 57. Multipurpose protection (MAPGAPC)
Characteristic
Value
Operation accuracy
±1.0% of the set value or ±20 ms
Table 58. Multipurpose analog protection (MAPGAPC) main settings
Parameter
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
Operate delay time
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
-
Control functions
Table 59. Emergency startup (ESMGAPC) main settings
Parameter
Function
Value (Range)
Step
Operation
ESMGAPC
Off
On
-
Motor stand still A
ESMGAPC
0.05...0.20 x I
n
0.01
Motor Protection and Control
1MRS756890 D
REM615
Product version: 3.0
Issued: 2010-06-29
ABB
47