Table 22. Insulation tests
Description
Type test value
Reference
Dielectric tests
IEC 60255-5 and
IEC 60255-27
• Test voltage
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
Impulse voltage test
IEC 60255-5 and
IEC 60255-27
• Test voltage
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
Insulation resistance
measurements
IEC 60255-5 and
IEC 60255-27
• Isolation resistance
>100 M
Ώ
, 500 V DC
Protective bonding
resistance
IEC 60255-27
• Resistance
<0.1
Ώ
, 4 A, 60 s
Table 23. Mechanical tests
Description
Reference
Requirement
Vibration tests (sinusoidal)
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Class 2
Shock and bump test
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Class 2
Seismic test
IEC 60255-21-3
Class 2
Table 24. Product safety
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Motor Protection and Control
1MRS756890 D
REM615
Product version: 3.0
Issued: 2010-06-29
28