GlobalBaseSel
: This is used to select GBASVAL function for reference of base
values.
SeqTypeUPol
: This is used to select the type of voltage polarising quantity i.e. Zero
seq and Neg seq for direction detection.
SeqTypeIPol
: This is used to select the type of current polarising quantity i.e. Zero seq
and Neg seq for direction detection.
SeqTypeIDir
: This is used to select the type of operating current quantity i.e. Zero seq
and Neg seq for direction detection.
9.4.3.1
Common settings for all steps
AngleRCA
: Relay characteristic angle given in degree. This angle is defined as shown
in Figure
. The angle is defined positive when the residual current lags the
reference voltage (Upol = 3U
0
or U
2
)
Upol = -3U
0
or
IN>Dir
RCA
Operation
-3U
2
IEC05000135-5-en.vsdx
IEC05000135 V5 EN
Figure 180:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting
range is -180° to +180°.
polMethod
: Defines if the directional polarization is from
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
341
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...