Figure 219:
High-availability Seamless Redundancy (HSR)
19.2.3
Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy
: redundant communication is activated when the parameter is set to
PRP-0
,
PRP-1
or
HSR
. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1
should be used primarily,
PRP-0
is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
1MRK 511 401-UUS A
Section 19
Ethernet-based communication
Bay control REC670 2.2 ANSI
573
Application manual