protection (reference angle set to 0) to trip if the active power from the generator is less
than about 2%. One should set the overpower protection (reference angle set to 180) to
trip if the power flow from the network to the generator is higher than 1%.
Underpower protection
Overpower protection
Q
Q
P
P
Operating point
without
turbine torque
Margin
Margin
Operate
Line
Operate
Line
Operating point
without
turbine torque
IEC09000019-2-en.vsd
IEC09000019 V2 EN-US
Figure 86:
Reverse power protection with underpower or overpower protection
8.12.3
Setting guidelines
SEMOD172134-4 v7
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
Operation
: With the parameter
Operation
the function can be set
Enabled
/
Disabled
.
Mode
: The voltage and current used for the power measurement. The setting
possibilities are shown in table
.
Table 26:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
A, B, C
*
*
*
A
A
B
B
C
C
S V
I
V
I
V
I
=
×
+
×
+
×
EQUATION2055-ANSI V1 EN-US
(Equation 64)
Arone
*
*
AB
A
BC
C
S V
I
V
I
=
×
-
×
EQUATION2056-ANSI V1 EN-US
(Equation 65)
PosSeq
*
3
PosSeq
PosSeq
S
V
I
= ×
×
EQUATION2057-ANSI V1 EN-US
(Equation 66)
AB
*
*
(
)
AB
A
B
S V
I
I
=
×
-
EQUATION2058-ANSI V1 EN-US
(Equation 67)
Table continues on next page
Section 8
1MRK 511 401-UUS A
Current protection
216
Bay control REC670 2.2 ANSI
Application manual
Содержание Relion REC670
Страница 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 42: ...36 ...
Страница 96: ...90 ...
Страница 274: ...268 ...
Страница 292: ...286 ...
Страница 298: ...292 ...
Страница 308: ...302 ...
Страница 470: ...464 ...
Страница 514: ...508 ...
Страница 608: ...602 ...
Страница 646: ...640 ...
Страница 656: ...650 ...
Страница 657: ...651 ...