Table 13:
ADE Non group settings (basic)
Name
Values (Range) Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation
TimerClass
Slow
Normal
Fast
-
-
Slow
Timer class
LON commands are available on the local HMI under
Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON
pot/Service Pin Messae/Generate service pin message
Table 14:
LON commands
Command
Command description
ServPinMess
Command with confirmation. Transfers the node address to the LON Network
Tool.
7.2
Optical budget calculation for serial communication
with LON
M11737-4 v2
Table 15:
Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation
-11 dB
- 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um
4 dB
-
0.3 dB/m plastic: 620 nm - 1mm
-
3 dB
Margins for installation, aging, and so on
5 dB
2 dB
Losses in connection box, two contacts (0.75 dB/contact)
1.5 dB
-
Losses in connection box, two contacts (1dB/contact)
-
2 dB
Margin for repair splices (0.5 dB/splice)
0.5 dB
-
Maximum total attenuation
11 dB
7 dB
Section 7
1MRK 511 425-UEN A
Establishing connection and verifying the LON communication
52
Bay control REC650 2.2 IEC
Commissioning manual
Содержание RELION REC650
Страница 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Страница 2: ......
Страница 12: ...6 ...
Страница 22: ...16 ...
Страница 26: ...20 ...
Страница 50: ...44 ...
Страница 54: ...48 ...
Страница 110: ...104 ...
Страница 118: ...112 ...
Страница 128: ...122 ...
Страница 129: ...123 ...