4.2.3.9
Technical data
Table 376: INTRPTEF Technical data
Characteristic
Value
Operation accuracy (Uo criteria with transi-
ent protection)
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
o
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5
4.2.3.10
Technical revision history
Table 377: INTRPTEF Technical revision history
Technical revision
Change
B
Minimum and default values changed to 40
ms for the
Operate delay time
setting
C
The
Minimum operate current
setting is add-
ed. Correction in IEC 61850 mapping: DO
BlkEF renamed to InhEF. Minimum value
changed from 0.01 to 0.10 (default changed
from 0.01 to 0.20) for the
Voltage start value
setting. Minimum value changed from 0 ms
to 40 ms for the
Reset delay time
setting.
D
Voltage start value description changed from
"Voltage start value for transient EF" to "Volt-
age start value" since the start value is effec-
tive in both operation modes. Added support
for calculated Uo. Uo source (measured/cal-
culated) can be selected with "Uo signal
Sel".
Voltage start value
setting minimum
changed from 0.10 to 0.05.
E
Min operate current
setting scaling corrected
to RMS level from peak level.
4.2.4
Admittance-based earth-fault protection EFPADM
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
341