Distributed busbar protection REB500
1MRK 505 352-BEN
Product version: 8.2
Issued: 2016-03-01
Revision: -
ABB
39
Table 33. Check zone criterion 87CZ (PDIF)
Function/ Parameter
Range/ Value
Accuracy
Min. fault current pick-up setting (I
kmin
) neutral
current detection
500 to 6000 A in steps of 200 A
±5% of I
N
at I
kmin
< I
N
±5% of I
kmin
at I
kmin
> I
N
*)
Stabilizing factor (k)
0.0 to 0.9 in steps of 0.05
-
CT ratio per feeder
50 to 10 000/1 A,
50 to 10 000/5 A,
adjustable via HMI
-
The check zone is used as an additional release criterion for busbar protection and operates zone-
independent.
*) For details about pickup accuracy see 1KHL020789-Aen-Verification-Pickup-Value
Recording facilities
Table 34. Event recorder
Event recorder
Bay unit
Central unit
System events
Protection events
Test events
100
1000
User activity events
-
2048
Table 35. Disturbance recorder (RDRE)
Options
analog channel
f
n
Recording period Sample rate selectable
4 currents and
5 voltages
50 Hz
60 Hz
4000 Hz
4800 Hz
2000 Hz
2400 Hz
1000 Hz
1200 Hz
Standard
X
-
1.5 s
3 s
6 s
Extended
X
-
20 s
20 s
20 s
Number of disturbance records = total recording time / set recording period (max.40)
Buffer overflow behavior is first in first out.
Independent settings for pre-fault and post-fault period (min. setting 200 ms).
Format: COMTRADE 99
Table 36. Central disturbance recorder (RDRE)
Options
analog channels
Recording period (sample rate fixed)
Standard
X
1.5 s
Extended
X
20 s
Recording of differential and restraint currents per phase (max. 4) and per buszone (max 32)
Number of disturbance records = total recording time / set recording period (max.40)
Buffer overflow behavior is first in first out.
Independent settings for pre-fault and post-fault period (min. setting 200 ms).
Format: COMTRADE 99