Distributed busbar protection REB500
1MRK 505 352-BEN
Product version: 8.2
Issued: 2016-03-01
Revision: -
ABB
29
11. Technical Data
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the
equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions,
the equipment meets the specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified
conditions, is able to perform its intended functions according to the specified requirements
Inputs, Outputs, Power Supply
Table 6. Analog inputs
Description
Value
Rated frequency
50/60 Hz
Operating range
Rated frequency ± 5 Hz
Current inputs
Rated current, I
n
1/5 A
1)
Thermal withstand capability:
For 1 s
For 10 s
Continuously
500 A
100 A
20 A
Dynamic current withstand:
Half-wave value
1250A
Input impedance
<20 m
Ω
Voltage inputs
Rated voltage, U
n
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
200 V AC/ 210 V AC/ 215 V AC/ 220 V AC
Voltage withstand:
Continuous
420 V rms
For 10 s
450 V rms
Burden at rated voltage
<0.05 VA
1) Phase currents or residual current
Содержание Relion REB500
Страница 1: ...Relion Distributed busbar protection REB500 Product Guide...
Страница 49: ......