4.1.3.2
Setting parameters for binary input/output module
PID-4050-SETTINGS v2
Table 32: IOMIN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Binary input/output module in operation
(On) or not (Off)
DebounceTime
0.001 - 0.020
s
0.001
0.001
Debounce time for binary inputs
OscBlock
1 - 40
Hz
1
40
Oscillation block limit
OscRelease
1 - 30
Hz
1
30
Oscillation release limit
Section 4
1MRK 502 066-UUS B
Binary input and output modules
82
Technical manual