14.2.12.4
Logic diagram
GUID-F0EF8D38-031B-4A8E-BD7D-60314F5DCD59 v2
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC08000469-1-en.vsd
Position including quality
Open/close position of
switch device
IEC08000469-1-EN V1 EN-US
Only the value, open/close, and status is used in this function. Time information is not used.
Input position (Value)
Signal quality
Output OPENPOS
Output CLOSEPOS
0 (Breaker intermediate)
Good
0
0
1 (Breaker open)
Good
1
0
2 (Breaker closed)
Good
0
1
3 (Breaker faulty)
Good
0
0
Any
Invalid
0
0
Any
Oscillatory
0
0
14.2.12.5
Signals
PID-3555-INPUTSIGNALS v4
Table 474: POS_EVAL Input signals
Name
Type
Default
Description
POSITION
INTEGER
0
Position status including quality
PID-3555-OUTPUTSIGNALS v4
Table 475: POS_EVAL Output signals
Name
Type
Description
OPENPOS
BOOLEAN
Open position
CLOSEPOS
BOOLEAN
Close position
14.3
Apparatus control APC
IP14560-1 v2
14.3.1
Functionality
M13444-3 v13
The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and grounding switches within a bay. Permission to trip is given after evaluation of
conditions from other functions such as interlocking, synchronism check, operator place selection
and external or internal blockings.
Apparatus control features:
1MRK 502 066-UUS B
Section 14
Control
825
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...