IEC16000040-1-en.vsdx
RESTORE
Voltage
start
START
TRIP
block
If
[StartFreqGrad<0
AND
df/dt < StartFreqGrad]
OR
[StartFreqGrad>0
AND
df/dt > StartFreqGrad]
Then
START
U < IntBlockLevel
BLKDMAGN
Rate-of-change
of Frequency
BLOCK
OR
BLKREST
>
f > RestoreFreq
tRestore
restore
AND
BLKTRIP
trip
AND
start
Start
&
Trip
output
logic
Definite timer
tReset
tDelay
Frequency
IEC16000040 V1 EN-US
Figure 156:
Simplified logic diagram for SAPFRC
9.3.7
Technical data
M14976-1 v9
Table 175:
SAPFRC Technical data
Function
Range or value
Accuracy
Operate value, start function
(-10.00-10.00) Hz/s
±10.0 mHz/s
Operate value, restore
enable frequency
(45.00-65.00) Hz
±2.0 mHz
Definite restore time delay
(0.000-60.000) s
±0.2% or ±100 ms whichever is
greater
Definite time delay for
frequency gradient trip
(0.200-60.000) s
±0.2% or ±120 ms whichever is
greater
Definite reset time delay
(0.000-60.000) s
±0.2% or ±250 ms whichever is
greater
1MRK 506 382-UEN A
Section 9
Frequency protection
Line distance protection REL650 2.2 IEC
313
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...