-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
-----
----
----
----
---
---
---
---
---
---
---
---
----
---
--
--
--
--
--
-
-
-
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
---
---
---
---
----
-
Real part (R) of Z in Ohms
Im
ag
ina
ry
pa
rt
(X
) o
f Z
in
O
hm
s
^ ^ ^ ^ ^ ^ ^ ^
^ ^ ^ ^ ^ ^ ^ ^
^ ^
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ztr
Ze
Zgen
SE
RE
Z(R,X)
R
Zline
Zone 2
relay
←
Z-line
120°
←
Lens is the locus
of constant rotor (power)
angle, e.g. 120°.
Lens' width determined
by the setting StartAngle
X
Position of the OOS
relay is the origin of
the R - X plane
Zone 1
limit-of-reach
→
circle depends on
the position of the
points SE and RE
X-line
determined
by the
→
setting
ReachZ1
IEC10000112-1-en.vsd
IEC10000112 V1 EN-US
Figure 64:
Construction of the lens characteristic for a power system
IEC10000113-2-en.vsd
d
Y
G
Generator
13.8 kV
13.8 kV
Power line
220 kV
Infinite power
system
Out-Of-Step
protection
OOSPPAM
Transformer
13.8 / 220 kV
System
equivalent
REG
Zgen(Rgen
, Xgen
)
Ztr(Rtr, Xtr)
Zline(Rline, Xline)
Zeq(Req, Xeq)
ReverseZ
ForwardZ(ForwardR, ForwardX)
ReverseR = Rg
ForwardR = Rtr + Rline + Req
ReverseX = Xd’
ForwardX = Xtr + Xline + Xeq
All impedances must be referred to the generator voltage 13.8 kV
SE
RE
d
Y
G
Generator
13.8 kV
13.8 kV
Power line
220 kV
Infinite power
system
Out-Of-Step
protection
OOSPPAM
Transformer
13.8 / 220 kV
System
equivalent
REG
Zgen(Rgen
, Xgen
)
Ztr(Rtr, Xtr)
Zline(Rline, Xline)
Zeq(Req, Xeq)
ReverseZ(ReverseR, ReverseX))
ForwardZ(ForwardR, ForwardX)
ReverseR = Rg
ForwardR = Rtr + Rline + Req
ReverseX = Xd’
ForwardX = Xtr + Xline + Xeq
All impedances must be referred to the generator voltage 13.8 kV
SE
RE
IEC10000113 V2 EN-US
Figure 65:
Example of an actual power system
To be able to automatically construct the lens characteristic for a system shown in
Figure
, the actual power system must be modeled as a two-machine equivalent
system, or as a single machine – infinite bus equivalent system, the following
information is necessary: Zgen(Rgen, Xgen), Ztr(Rtr, Xtr), Zline(Rline, Xline),
Zeq(Req, Xeq), and the setting
StartAngle
, for example 120 degrees. All
impedances must be referred to the voltage level where the out-of-step protection
relay is placed; in the case shown in Figure
terminals of the generator and, therefore, the previous quantities shall be referred to
Section 6
1MRK 506 382-UEN A
Impedance protection
142
Line distance protection REL650 2.2 IEC
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...