3.13.2
Functionality
When the Test mode functionality TESTMODE is activated, all the protection
functions in the IED are automatically blocked. It is then possible to unblock every
function(s) individually from the LHMI to perform the required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes normal
operation. However, if during TESTMODE operation, power is removed and later
restored, the IED remains in TESTMODE with the same protection functions blocked
or unblocked as before the power was removed. All testing is done with the actually
set and configured values within the IED. No settings are changed to avoid mistakes.
3.13.3
Operation principle
IED functions can be tested in test mode. The IED can be set to test mode either by
activating the input
SIGNAL
on the function block TESTMODE, or setting
TestMode
to "On" in the LHMI.
When the IED is in test mode, the
ACTIVE
of the function block TESTMODE is
activated. The outputs of the function block TESTMODE show the cause of the
Test
mode
is set to "On" state, that is, input from configuration (
OUTPUT
output is
activated) or setting from LHMI (
SETTING
output is activated).
When the IED is in test mode, the yellow STARTLED flashes and all functions are
blocked. Any function can be unblocked individually regarding functionality and
event signalling.
Forcing of binary output signals is only possible when the IED is in test mode.
Most of the IED functions can be individually blocked by local HMI settings. To
enable blockings, the IED must be in test mode (output
ACTIVE
is activated). When
leaving the test mode and entering the normal mode, the blockings are disabled and
everything is set to normal operation. In the test mode, all testing can be done with the
actually set and configured values within the IED. If any setting values are changed
during the testing, they should be changed back to original values before entering the
normal mode.
The blocked functions are still blocked next time entering the test mode, if the
blockings are not reset.
The blocking of a function concerns all the output signals from the actual function, so
no outputs are activated.
When a binary input is used to set the IED in test mode and a parameter
that requires restart of the application, is changed, the IED re-enters
test mode and all functions are blocked, also the functions that were
unblocked before the change. During the re-entering to test mode, all
functions are temporarily unblocked for a short time, which may lead
Section 3
1MRS757256 F
Basic functions
74
PML630/Compact Load-Shedding Solution
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...