Figure 8:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
•
To check the status of the output circuits driving the output relay via the
LHMI, select
Main menu/Monitoring/I/O status/Binary output modules
and then navigate to the board with the actual binary output to be checked.
•
Test and change the relay state manually.
1.
To set the IED to test mode, select
Main menu/Test/IED test mode/
TestMode
and set the parameter to
On
.
2.
To operate or force the output relay to operate, select
Main menu/Test/
Forcing/Binary output values
and then navigate to the board with the
actual binary output relay to be operated/forced.
3.
Select the BOn_PO to be operated/forced and use
and
or
to
operate the actual output relay.
In PCM600, only the result of these operations can be checked by right-
clicking the product and selecting Signal Monitoring tool and then
1MRS756801 A
Section 5
Troubleshooting
630 series
35