3.2.3
Input/output signal interface
Table 6:
Binary input interface
Hardware module
instance
Hardware channel Usage
COM
BI1
Generator circuit breaker close
COM
BI2
Generator circuit breaker open
COM
BI3
Generator circuit breaker truck close
COM
BI4
Generator circuit breaker truck open
COM
BI5
Earthing switch close
COM
BI6
Earthing switch open
COM
BI7
NGR switch close
COM
BI8
NGR switch open
COM
BI9
Operate signal from AVR
COM
BI10
Operate signal from turbine
COM
BI11
Lockout reset
COM
BI12
Generator circuit breaker gas pressure (lockout)
COM
BI13
Generator circuit breaker spring charged
COM
BI14
Voltage transformer MCB open
The IED outputs are categorized as power outputs (POx) and signal outputs (SOx).
The power outputs can be used for starting and stopping the motor. The signal outputs
are not heavy-duty outputs. They are used for alarm or signalling purposes.
Table 7:
Binary output interface
Hardware module
instance
Hardware channel Usage
PSM
PO1
Master Trip 1 (generator circuit breaker open)
PSM
PO2
Generator circuit breaker close enable signal
PSM
PO3
Master Trip 2 (generator circuit breaker open)
PSM
PO4
Operate from directional over power protection
PSM
PO5
Operate from differential protection
PSM
PO6
Operate from frequency protection
PSM
SO1
Common generator circuit breaker operate signal
PSM
SO2
Common generator circuit breaker start signal
PSM
SO3
Generator circuit breaker trip circuit and monitoring alarm
The IED measures the analog signals needed for protection and measuring functions
via galvanically-isolated matching transformers. The matching transformer input
channels 1…7 are intended for current measuring, and the channels 8...10 for voltage
measuring.
1MRS757582 C
Section 3
REG630 variants
REG630
27