Different Modbus indications originating from the same IEC 61850
data attribute have an identical UID. It is therefore recommended to
use the Modbus address as the identification instead of the UID.
Data value identification bits 5..0
Coding of the event data value is one bit, two bits or 32 bits. The coding depends on
the IEC 61850 common data class which is the origin of the Modbus data in question.
Table 28:
Modbus event value alternatives
Object derived from
IEC 61850 Class
Meaning
One Bit Data
Value
Two Bit Data
Value
32 bit Data
Value
SPS
Single Point Status
X
SPC
Single Point Status of a controllable
object
X
DPS
Dual Point Status
X
DPC
Dual Point Status of a controllable
object
X
ACT
Trip status
X
ACD
Start/Pick-up status
X
INS/INC
Integer status
X
Table 29:
Interpretation of the one-bit data value
Register 49261 binary coded value
Meaning
xxxx.xxxx.xxxx.xxx0
Object in OFF position
xxxx.xxxx.xxxx.xxx1
Object in ON position
Table 30:
Interpretation of the two-bit data value
Register 49261 binary coded value
Meaning
xxxx.xxxx.xxxx.xx00
Object in intermediate position (changing)
xxxx.xxxx.xxxx.xx01
Object in ON (close) position
xxxx.xxxx.xxxx.xx10
Object in OFF (open) position
xxxx.xxxx.xxxx.xx11
Object in faulty position
In case of a DPS/DPC two-bit event value (Data value identification
= 2), the data object ID registers 49259 and 49260 always refer to the
Modbus address or UID of the CLOSE momentary value bit.
Table 31:
Interpretation of the integer status data value
Register address
Meaning
49261
Higher 16 bit part of the 32 bit integer value
49262
Lower 16 bit part of the 32 bit integer value
1MRS757645 B
Section 3
Vendor-specific implementation
620 series
53
Communication Protocol Manual