![ABB Relion 620 Series Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_protocol-manual_3412484051.webp)
Table 24:
UDR scaling alternatives
Scaling alternative Setting
Description
No scaling
No change is made to the sourceValue
Ratio scaling
UDRScaleArg1 = Min in
Uses all 4 scaling arguments
UDRScaleArg1...UDRScaleArg4.
UDRScaleArg2 = Max in
UDRScaleArg3 = Min
out
UDRScaleArg4 = Max
out
Multiplicative
scaling
UDRScaleArg1 =
Multiplicand
Uses the argument UDRScaleArg1 (Min in)
Divisior scaling
UDRScaleArg1 = Divisor Uses the argument UDRScaleArg1 (Min in)
Ratio scaling Operation
The sourceValue is to be checked for saturation. If it is less than Min in, the UDR result
value is equal to Min out. If it is greater than Max in, the UDR result value is Max out.
Otherwise the UDR result value is calculated as
•
X = (MaxOut-MinOut)/(MaxIn-MinIn)
•
UDR_ResultValue = X × sourc (MinOut - X × MinIn)
Multiplicative scaling Operation
UDR_resultValue = sourceValue × multiplicand
Divisior scaling Operation
UDR_resultValue = sourceValue/Divisor
3.4.8.8
UDR register configuration
UDR registers are read-only registers mirrored both on input register (3x) and holding
register (4x) areas. After adding a Modbus register value into the user-definable
memory area, it is possible to leave it in exactly the same format as the source Modbus
value. Alternatively, it is possible to change the user-definable value outlook to better
suit the Modbus master.
The UDR value configuration can be divided in three parts.
•
Initial properties. Redefine the user-definable register type and how the Modbus
value source is retrieved.
•
Rescaling. Applies a new scaling to the UDR value.
•
Presentation. Modifies the presentation of the UDR value. These modifications
are only needed for special retrofit cases.
Columns in the tool do not necessary appear in the same order as in the table.
1MRS757645 B
Section 3
Vendor-specific implementation
620 series
45