GUID-8C044A41-24DE-44D0-AAB4-E52D6BD61BC5 V1 EN
Figure 501:
Connection of voltages for the protection relay and signals used in
synchrocheck
9.3.6
Signals
Table 895:
25 Input signals
Name
Type
Default
Description
V_BUS
SIGNAL
0=False
Busbar Voltage
V_LINE
SIGNAL
0=False
Line Voltage
CL_COMMAND
BOOLEAN
0=False
External closing request
BYPASS
BOOLEAN
0=False
Request to bypass synchronism check and voltage
check
BLOCK
BOOLEAN
0=False
Blocking signal of the synchro check and voltage check
function
Table 896:
25 Output signals
Name
Type
Description
SYNC_INPRO
BOOLEAN
Synchronizing in progress
SYNC_OK
BOOLEAN
Systems in synchronism
CL_FAIL_AL
BOOLEAN
CB closing failed
Table continues on next page
Section 9
1MAC059074-MB A
Control functions
988
615 series ANSI
Technical Manual